318TQ to BS 6500

Application and Description

These cables can be used either in dry, humid or wet places or in contact with oil or grease, in weather conditions and under weak mechanical stress, they are suitable for power supply to small appliances in industrial plants, machine shops, heating plates, portable lamps, farming equipment etc. They are also suitable for caravans and camping equipment. 318TQ is equivalent to harmonized code H05BN4-F.

Cable Construction

Fine bare copper strands

Stranding to BS 6360 CL-5 or IEC 60228 CL-5

EPR(Ethylene Propylene Rubber) rubber EI7 insulation

CSP(Chlorosulphonated Polyethylene) outer jacket EM7

Core Identification

2 Cores : Brown, Blue

3 Cores : Brown, Blue and Green/Yellow

4 Cores : Brown, Grey, Black and Green/Yellow

5 Cores : Brown, Blue, Grey, Black and Green/Yellow

6 cores and above : white insulation with black numerals

Technical Characteristics

Working voltage : 300/500 volts

Test voltage : 2000 volts

Flexing bending radius : 6xOverall diameter

Fixed bending radius : 4xOverall diameter

Temperature range : -20°C to +90°C

Maximum short circuit temperature : +25°C

Flame retardant : IEC 60332.1

Insulation resistance : 20 MΩxkm

Cable Parameter

AWG (No. of Strands/Strand Diameter)

No. of Cores × Nominal Cross Sectional Area

Nominal Thickness of Insulation

Nominal Thickness of Sheath

Nominal Overall Diameter

Nominal Weight

 

# × mm²

mm

mm

mm

kg/km

3182TQ

18(24/32)

2x0.75

0.6

0.8

6.5

66

17(32/32)

2x1

0.6

0.9

7.1

79

3183TQ

18(24/32)

3x0.75

0.6

0.9

7.1

80

17(32/32)

3x1

0.6

0.9

7.6

94