H07BN4-F WIND90

Application and Description

These cables are made with synthetic rubbers having an excellent temperature resistance and can be used either in dry, humid or wet places or in contact with oil or grease, in weather conditions and under medium mechanical stress, for example power supply to equipment in industrial plants, large size boilers, heating plates, portable lamps, electrical tools such as drilling machines, disk saws, portable engines and machines, building and farming equipments etc.

These cables are also suitable for stationary equipments, for example designed for wind-tower application, the particular conductor Cable Construction and the used materials have improved the cable torsion resistance (max 150°/m), key requirement for drop cables in windgenerators, on plaster in temporary buildings and builders huts, and wiring in machinery elevators or similar.

Suitable for caravans and camping equipment. Especially recommended for service temperature up to 90oC together with good resistance to hot grease and oil. Therefore these cables are ideal for use in plants and industries dealing with grease, oil or oil emulsion treatments, transformation or handling. 

Standard and Approval

  • CEI 20-19 p.12, CEI 20-35 (EN 60332-1), IEMMEQU HAR IEC 60245-4, IEC 60754-1/2, ROHS compliant

Cable Construction

Technical Characteristics

Fine bare copper strands

Strands to VDE-0295 Class-5, IEC 60228 Class-5

EPR(Ethylene Propylene Rubber) rubber EI7 insulation

Color code VDE-0293-308

Special polychloroprene rubber outer jacket EM7

 

Working voltage

450/750 volts

Test voltage

2500 volts

Flexing bending radius

6.0 x O

Fixed bending radius

4.0 x O

Temperature Range

-40oC to +90oC

Wind energy

-15oC to +90oC

Maximum Short Circuit Temperature

+250oC

Flame retardant

IEC 60332.1C2/NF C 32-070

Insulation resistance

20 MΩ x km