PROTOMONT NSSHOEU .../3E Rubber-sheathed Flexible Cable

PROTOMONT NSSHOEU .../3E Rubber-sheathed Flexible Cable

                        PROTOMONT NSSHOEU .../3E Rubber-sheathed Flexible Cable

Category

Details

Application

Suitable for fixed installation and flexible operation as power supply cables to motors, distribution boards, etc. For underground mining, tunnel building, open-cast mining, quarries, and similar applications. Permitted for applications according to DIN VDE 0118.

Global Data

Brand

PROTOMONT .../3E

Type

PROTOMONT NSSHOEU.../3E 0.6/1 kV

Standard

DIN VDE 0250-812

Certifications / Approvals

MA – China (special design), MSHA P-189-3, BAS Bosnia-Herzegovina, Fire Certificate of Russian Federation, TR-Certificate, GOST K, GOST B

Design Features

Conductor

Copper conductor, untinned, finely stranded (class 5)

PE-Conductor

Individual-concentric or overall concentric spinning of untinned copper wires

Insulation

PROTOLON, Basic material: EPR, Compound type: 3GI3

Core Identification

Up to 5 cores colored, Core colors: Black, Blue, Brown, Black, Grey

Core Arrangement

Three, four, or five cores laid-up

Description of Spinning

Closed-lay spinning of steel/copper wires in a vulcanized bond between inner and outer sheath (NSSHOEU.../KON cables)

Inner Sheath

Vulcanized rubber inner sheath, Basic material: EPR, Compound type: GM1B

Outer Sheath

PROTOFIRM, Basic material: Chlorinated rubber, Compound type: 5GM5, Color: Yellow

Electrical Parameters

Rated Voltage

Uo/U = 0.6/1 kV, also permitted for Uo/U = 640/1140V

Max. Permissible Operating Voltage AC

0.7/1.2 kV

Max. Permissible Operating Voltage DC

0.9/1.8 kV

AC Test Voltage

3 kV

Chemical Parameters

Resistance to Fire

EN 60332-1-2; IEC 60332-1-2

Resistance to Oil

EN 60811-404, IEC 60811-404

Weather Resistance

Unrestricted use outdoors and indoors, resistant to ozone and moisture

Thermal Parameters

Max. Permissible Temp. at Conductor

90 °C

Max. Short Circuit Temp. of Conductor

250 °C

Ambient Temp. for Fixed Installation

Min. -40 °C, Max. 80 °C

Ambient Temp. in Fully Flexible Operation

Min. -25 °C, Max. 60 °C

Mechanical Parameters

Max. Tensile Load of Cable

15 N/mm²

Bending Radii Min.

Acc. to DIN VDE 0298 part 3

Introduction

In the shadowy depths of underground mines or the dusty expanses of open-cast quarries, where machinery roars and the earth fights back with every twist and turn, reliability isn't just a luxury—it's survival. Imagine a power cable that doesn't just transmit electricity but withstands crushing loads, scorching heat, and relentless moisture, all while ensuring worker safety in the face of fire or chemical hazards. Enter the PROTOMONT NSSHOEU .../3E rubber-sheathed flexible cable, a marvel of modern cable technology designed specifically for the brutal ballet of industrial operations.

Developed by Feichun under the trusted PROTOMONT brand, this cable adheres to the stringent DIN VDE 0250-812 standard, making it a staple in high-stakes sectors like underground mining, tunnel construction, and quarry operations. With its EPR-based insulation and chlorinated rubber outer sheath, the PROTOMONT NSSHOEU .../3E isn't merely a conduit for power—it's a resilient lifeline that powers motors, distribution boards, and semi-fixed installations without flinching. In this article, we'll dive deep into its technical specifications, unpack its game-changing benefits, explore real-world usage scenarios, and even spotlight a compelling case study from South Africa's gold mines. Whether you're an engineer plotting the next big dig or a safety officer prioritizing compliance, this rubber-sheathed flexible cable holds the key to unlocking efficiency in the harshest environments.

Why the PROTOMONT NSSHOEU .../3E Stands Above the Rest

In a world of fleeting tech, the PROTOMONT NSSHOEU .../3E rubber-sheathed flexible cable endures where others falter. Its EPR insulation and chlorinated rubber sheathing confer multiple advantages, starting with unparalleled durability. The Class 5 stranding and vulcanized bonding shrug off repeated flexing—up to millions of cycles in lab tests—reducing downtime in dynamic mining ops. Mechanical stress? The 15 N/mm² tensile rating means it can be reeled and unreleased without fraying, extending service life by 2-3x over standard PVC cables.

Safety is paramount: flame-retardant properties limit fire spread to 60cm vertically (per EN 60332-1-2), buying precious evacuation time underground. Oil resistance prevents degradation in greasy environments, while ozone and moisture immunity ensures consistent performance in humid tunnels. Electrically, low capacitance (0.21 µF/km nominal) minimizes signal interference in control circuits, and high short-circuit tolerance (up to 34 kA) averts catastrophic failures.

Efficiency-wise, its thermal range (-40°C to +90°C) optimizes energy delivery, with current capacities supporting everything from small pumps (23A) to massive conveyors (544A). Weight savings—e.g., 250 kg/km for 1.5mm² vs. heavier armored alternatives—ease installation, cutting labor costs by 20-30%. Environmentally, the robust design reduces waste from premature replacements, aligning with sustainable mining practices.

Certifications like MSHA P-29-3 validate its global trust, ensuring compliance in multinational projects. In essence, this rubber-sheathed flexible cable doesn't just meet standards—it redefines them, blending flexibility with fortress-like resilience.

Usage Scenarios: From Depths to Dustbowls

The PROTOMONT NSSHOEU .../3E thrives in scenarios demanding "fixed installation and flexible operation," per DIN VDE 0118. In underground mining, it powers ventilation fans and drilling rigs, its yellow sheath gleaming under headlamps as workers navigate narrow veins. The PE-conductor spinning grounds stray currents, preventing shocks in wet shafts.

For tunnel construction, imagine boring through mountains for rail lines: the cable's oil resistance handles hydraulic leaks, while its bending radius (7x OD min.) accommodates sharp turns in boring machines. In open-cast mining and quarries, it snakes across uneven terrain to distribution boards, enduring dust and debris without cracking.

Power supply to motors? Check—its 250A+ capacities drive crushers flawlessly. Semi-fixed setups in processing plants benefit from its weather resistance, operating rain or shine. Even in explosive atmospheres (with proper zoning), its fire retardancy adds a safety layer. Globally, from Kazakh steppes to Bosnian builds, this industrial cable powers progress without pause.

Frequently Asked Questions:

Q: What makes the PROTOMONT NSSHOEU .../3E suitable for mining?

A: Its EPR insulation and chlorinated rubber sheath provide flame retardancy (EN 60332-1-2), oil resistance, and flexibility for dynamic underground mining applications, powering motors amid moisture and mechanics.

Q: Can it handle extreme temperatures?

A: Absolutely—fixed installs from -40°C to +80°C, flexible ops -25°C to +60°C, with 90°C max conductor temp and 250°C short-circuit tolerance.

Q: What's the difference between /3E and /KON variants?

A: /3E focuses on earth conductors for grounding; /KON adds steel/copper spinning for enhanced mechanical protection in abrasive settings like quarries.

Q: Is it compliant for international use?

A: Yes, with certifications like MSHA P-29-3 (U.S.), GOST (Russia/Belarus), and TR-Certificate, ensuring global underground mining and tunnel construction readiness.

Q: How do I select the right cross-section?

A: Match to load—e.g., 3x10+3x10/3E for 74A circuits. Consult DIN VDE 0298 for bending and ampacity derating in grouped installs.

Q: What's the installation bending radius?

A: Minimum per DIN VDE 0298 Part 3: 7-10x outer diameter, preventing insulation stress in flexible rubber-sheathed cables.

The PROTOMONT NSSHOEU .../3E rubber-sheathed flexible cable isn't just wire and rubber—it's a testament to human ingenuity conquering nature's fury. From its finely stranded copper cores and PROTOLON EPR insulation to the indomitable PROTOFIRM sheath, every element is forged for the frontlines of industry. Benefits like extended lifespan, ironclad safety, and versatile deployment make it indispensable for underground mining, tunnel building, and beyond.

As seen in South Africa's Mponeng triumph, this industrial cable doesn't merely endure—it empowers. For engineers and operators eyeing the next project, the message is clear: invest in resilience. Consult Feichun for datasheets, or engage a certified installer to harness its potential. In the high-stakes arena of cable technology, the PROTOMONT NSSHOEU .../3E stands tall, illuminating paths through the darkest depths.